技术属性

一般信息
Product type Power cables
Weight 1170 kg/km
电气特性
Nominal voltage U0/U: 0,6/1 kV AC rms according to IEC
Max. conductor resistance at 20°C 0.868  Ω/km
Test voltage 4  kV
Current rating according to VDE 0276-603
产品设计
Conductor abbreviation 4x35 RE
Conductor design IEC 60228 class 1: solid conductor
Conductor material Aluminium
Min. outer diameter 27
Conductor shape Round
Nominal conductor cross-section (metric) 35  mm²
Conductor count/size 4G35 RE
Shielded

Core identification Colours
Shape of cable Round
Outer sheath colour black
Filling compound over the core assembly

Conductor colour code VDE 0293-308
Number of cores 4
Core insulation basic material Polyvinylchloride
N-German standard cables NAYY-J
Basic material of outer sheath Polyvinylchloride
Including protective earth

Core insulation basic material, short form PVC
Max. outer diameter 31
Basic material of outer sheath, short form PVC
产品特点
Flame-retardant

PWIS-free according to VDMA 24364-B2-L
Installation temperature min. -5
UV-resistant

Minimum bending radius in mm, fixed installation 372.0  mm
Suitable for underground installation direct, in cable trench, in protective cable conduit
PWIS-free

Application area Fixed installation
Oil-resistant

Max. assembly temperature 50
Minimum bending radius, stationary 12 x outer diameter
Temperature, fixed installation -40 °C to 70 °C max. conductor temperature:
Flame retardance according to IEC 60332-1-2
UV-resistant according to EN 50525-1 (cables with a black sheath are suitable for permanent outdoor use)
For torsional load

Halogenfree

认证和标准
HAR-certified

Product standard VDE VDE 0276-603
Flame retardance tested according to UN/ECE-R118

CE marked

CPR fire class Eca
VDE certified

EAC certification number ЕАЭС RU С-DE.АЮ64.В.00091/19, ЕАЭС RU С-DE.АЮ64.В.00110/20
EAC-certified

文档
产品系列列表
All articles from NAYY
Article number Conductor abbreviation N-German standard cables Imp outer dia cable sheath min Min. outer diameter Imp outer diam cable sheath max Max. outer diameter Alu index calc export Aluminium index Copper index calc export Weight
1550056 1x50 RM NAYY-O 145.000 298 kg/km
1552010 4x35 RE NAYY-J 27 31 406.000 1170 kg/km
1552011 4x50 SE NAYY-J 28 33 580.000 1305 kg/km
1552012 4x70 SE NAYY-J 32 37 812.000 1730 kg/km
1552013 4x95 SE NAYY-J 36 41 1102.000 2205 kg/km
1552014 4x120 SE NAYY-J 40 46 1392.000 2655 kg/km
1552015 4x150 SE NAYY-J 43 48 1740.000 3150 kg/km
1552016 4x185 SE NAYY-J 48 53 2146.000 3925 kg/km
1552017 4x240 SE NAYY-J 2784.000 4880 kg/km
1552022 1x300 RM NAYY-O 870.000 1379 kg/km
3036547 1x70 RM NAYY-O 203.000 410 kg/km
3036548 1x95 RM NAYY-O 276.000 570 kg/km
3036549 1x120 RM NAYY-O 348.000 620 kg/km
3036550 1x150 RM NAYY-O 435.000 735 kg/km
3036551 1x185 RM NAYY-O 536.000 845 kg/km
3036552 1x240 RM NAYY-O 696.000 1100 kg/km